instruction
stringlengths
28
338
input
float64
output
stringlengths
40
290
What are the steps you would take to diagnose and resolve the error M7112-Visual software model number is inconsistent with PLC model number in a machine code of KM-ASSYM3-06 error id of 113?
null
The solution to the M7112 error is to check that the visual software model number matches the PLC model number. If both numbers are correct, then the error may be caused by a mismatch between the cable connections, power supply,
What is M110-Y axis rear limit abnormality, and how does it relate to X6 machine code? How does the KM-ASSYM2-10 error id of 41 relate to these issues, and what is the recommended solution for resolving the problem?
null
The solution to the M110-Y axis rear limit abnormality (X6) error may involve adjusting the rear limit switch to ensure it is properly aligned with the rear of the bed. If it is still inaccurate after
Question: What is the error message M7019 and what does it mean?
null
The solution to the M7019 error is to first execute the device to return to its origin before attempting any further actions. This error occurs when a device is not properly synchronized with its origin, and it requires the device to be returned to
What error message is being displayed on the M7072-Z-axis servo?
null
The error M7072-Z-axis servo NO readly(X17)&ERROR typically indicates an issue with the Z-axis servo driver circuitry. It is recommended to first check for wiring errors or loose connections
What steps can be taken to resolve the M7098 error in machine code KM-ASSYM2-01 when the current position of the PCB board exceeds the safe distance?
null
The error M7098 indicates that the PCB board is not placed properly. This issue can be resolved by rechecking the PCB board's position and ensuring that it is within the safe distance allowed for PCB placement. If
What is the M7064-X-axis servo error message?
null
The solution to the M7064-X-axis servo NO readly(X14)&ERROR error is to check the abnormality of the X-axis servo driver. You can do this by examining the logs
What does the M80-EMO&&DOOR is on error code indicate? How can the safety door and emergency stop switch be checked to determine the cause of the error?
null
The solution for the error M80-EMO&&DOOR is on. Please check the safety door and emergency stop switch (X6) is to verify that the safety door is closed and the emergency stop switch is disabled before starting the machine
What is the error message "M7054-The current dispensing amount is too small, please increase machine code of KM-ASSYM3-06 error id of 55"? What is the significance of this error and how does it relate to the solution you are referring to?
null
The error M7054 usually occurs when the dispensing amount is less than the minimum amount required. To solve this error, you need to increase the dispensing amount by adjusting the settings on your printer or using a different ink cartr
What is the error message "The backend PLC2-M7055-Product No. 3 failed to scan the code" and what is the possible cause of this error?
null
The solution for the error described as "The backend PLC2-M7055-Product No. 3 failed to scan the code, please check whether the barcode is abnormal?" is to either verify that the barcode is
Why is the Equipment model setting not set in the solution with the error M81-Equipment model setting has not been set, please set the device model machine code of KM-ASSYM3-03 error id of 12? What is the KM-ASSYM3-
null
The solution for the error "M81-Equipment model setting has not been set, please set the device model" is to open the device manager, identify the problematic device, right-click and select "Properties," then click on
What is the meaning of the error message M124-CCD? What is KM-ASSYM2-03? What is the ARM machine code? What is the error id of 55? What is the cause of this error?
null
This error usually indicates a hardware issue with the CCD camera controller in your robot arm. It may require updating or reprogramming the controller's firmware or software, or troubleshooting the controller's connections to ensure the arm receives
What is a KM-ASSYM4-07 assembly line machine code and what is the nature of the error described as "Alarm: initial startup, there is material in the assembly line machine code of KM-ASSYM4-07 error id of 33"?
null
To fix the error described as Alarm: initial startup, there is material in the assembly line, you'll need to identify the source of the material and clear it from the assembly line. This may require adjusting your manufacturing processes or stopping production
How long has the PLC1-M7022 been waiting for the scan code result before timing out with error id 183? Have any changes been made to the machine code or scan code settings in the KM-ASSYH2-05 system? Is there a way to increase
null
The solution to the error Post-stage PLC1-M7022-timed out 10S while waiting for the scan code result, is to increase the time out duration for the scan code in the device configuration settings.
What does the "M96-The work area blocking cylinder is rising abnormally (X26)" error message mean? This error message indicates that the work area blocking cylinder is rising abnormally. The work area blocking cylinder is typically used to protect the work area from accidentally being
null
Check if the cylinder is stuck when rising. If the movement is restricted and the cylinder cannot fully extend, then the error M96-The work area blocking cylinder is rising abnormally (X26) may be caused by
What is the error code M7082 and what does it mean? Could you provide more information about the context in which this error occurred?
null
The solution for the M7082-MARK point recognition failed error is to reset the device's memory and perform the point recognition process again. If the issue persists, it may be necessary to consult the device's manual or contact
What is the M7039-The work area blocking cylinder is abnormally descending (X34), please check whether the cylinder is stuck when descending error message being displayed in the controller?
null
The solution for the M7039 error is to manually lower the cylinder and verify that it moves freely. If the cylinder only moves when lowered, it may be stuck and the maintenance team should be consulted for further investigation and repair
Why is there an error message M7073 with reference to KM-ASSYM3-06 error id 74 related to the Z-axis limit? How can I check whether the slide table is touching the limit of the machine?
null
The solution to M7073 error that states the limit on the Z axis is abnormal, close to the origin end (X13) is to check whether the slide table touches the limit. This can be accomplished by physically inspecting
Here are a few possible questions related to the error you mentioned: 1. What is the M105 error code and what does it mean? 2. Can you explain the right limit abnormality (X5) error? 3. What could cause this error to occur in a KM
null
To resolve a M105-X axis right limit abnormality (X5) error, you should first ensure that the printer has a manual mode enabled. Then, you can adjust the print bed's position and level until the error
Sure! Here are a few questions to help you troubleshoot the issue: 1. Are the X-axis servos physically connected to the machine? If not, check the wiring and ensure the servos are properly connected to the machine. 2. Are there any loose or damaged connections in the
null
The solution for the M104-X axis servo NO readly and ERROR (X10) can vary depending on the specific issue, but it often involves checking the connections between the servo and the motherboard, confirming that
What does the error "pad pushes out cylinder 1\_moving position alarm machine code of KM-ASSYM4-03 error id 8" mean?
null
The solution for the "pad pushes out cylinder 1_moving position alarm" error would likely involve checking the wiring and making sure that the pad and cylinder are properly aligned. It is recommended to contact a professional mechanic if
What is the error message KM-ASSYH2-06 that describes the problem with the front section PLC1-M7038 and the working area side positioning cylinder protruding abnormally? What can the sensor X54 determine in this situation?
null
The error message indicates that the working area side positioning cylinder protrudes abnormally. The possible solution could involve checking the sensor X54 to ensure that it is functioning correctly. If the sensor is malfunctioning, it may need
What could be causing the weighing machine to reset and resulting in the error code M7102-Weighing machine reset failed machine code of KM-ASSYM1-01 with error id of 103? Could the issue be related to a problem with the machine's software
null
M7102-Weighing machine reset failed error typically occurs when the machine cannot initialize due to an incorrect password or issue with its software. To resolve this, consult the owner manual for instructions on resetting the machine and updating its firm
Can you provide more context about what "Communication Abnormality" refers to in this error? What is the purpose of the backend-M7021-PLC machine code in this system, and what is the function of the KM-ASSYH2-04 error id?
null
The solution for a communication abnormality between backend-M7021-PLC and other devices may involve checking for hardware or software issues, ensuring proper wiring and connections, updating device drivers and firmware, or troubleshooting
What is the possible cause of the M88-The discharging operation of the front waiting area has timed out, please check whether the machine is stuck machine code of KM-ASSYM3-03 error id of 19?
null
The solution for M88 error is to check whether the machine is stuck by resetting the waiting queue or contacting technical support for further assistance.
1. What is the KM-ASSYM5-08 error code and what does it mean? 2. What is the M134-CCD timed out waiting for arm START OK signal? 3. What steps can be taken to fix the error?
null
The M134-CCD error occurs when the Arduino attempts to communicate with the CCD module over the serial port, but the module does not respond within a specified time period. This error can be resolved by adjusting the b
What is the error code M7093-TE LINK timeout in machine code of KM-ASSYM5-06, and what does it mean how it is related to error id 94?
null
The M7093-TE link timeout error typically occurs when there is a problem with the connection between two devices. To resolve this issue, you will need to check the cable connections and ensure that they are secure. If the problem persists
Sure, here's a sample question about this error: What could be causing a discharge blocking cylinder rise timeout alarm in a KM-BFT machine with error id 23, and how can this issue be resolved?
null
The solution for a discharge blocking cylinder rise timeout alarm typically involves resetting the alarm, checking the cylinder position sensor, and ensuring that the cylinder is not obstructed by debris or other items.
What error code M7064-X-axis servo NO readly(X15)&ERROR is indicating and what does it mean?
null
The solution for the error M7064-X-axis servo NO ready(X15)&ERROR could involve several steps. First, unplug and plug in the X-axis servo driver to check if the issue is with
Question: What is the M136-CCD reading arm error code and how can it be resolved? Answer: M136-CCD reading arm Arrive signal timed out, machine code 67. This error code indicates an issue with the communication between the reading arm and the
null
To fix the M136-CCD reading arm "Arrive signal timed out" error, you can try adjusting the timing settings of the reading arm, resetting the communication between devices, or checking for any possible interference with other
What is the M80-EMO&&DOOR error message, and what is its machine code of KM-ASSYM3-08 error id of 11?
null
The solution for the error M80-EMO&&DOOR is on. Please check the safety door and emergency stop switch (X6) is to verify that the safety door is closed and the emergency stop switch is disabled before starting the machine
What is the purpose of this error message and what does it mean for the work area?
null
The solution for the M75-Start error is to select the work area status as "Clear" before starting the machine. If the work area is not clear, the machine will not start and will display this error message.
What is the name of the device that is experiencing the issue with the M7010-5 point detection failed error in KM-ASSYM4-05 machine code? Is there any information available regarding the previous attempts made to resolve the error or any relevant context that could be helpful in
null
The M7010-5 point detection failed error typically occurs when the device's camera is unable to detect points due to poor lighting conditions, camera focus, or hardware problems. To resolve this issue, try cleaning the camera lens, adjust
What is the intended machine code for the M7087-TE LINK out of range error found during the execution of KM-ASSYM4-05? What is the expected behavior of the system when this error is encountered? Is there any specific software or hardware configuration that could cause this error
null
The error M7087-TE LINK out of range typically occurs when the TTL setting of a router or access point is too low. To resolve this issue, you can increase the TTL setting on the router or access point,
What is the M128-CCD error in the given context?
null
The solution for the error described as M128-CCD failed to send command to ARM is to check the connection between the CCD camera and the ARM control unit. If the connection is loose or damaged, tighten it or replace it
What is the error code M7114-Timeout waiting for dispensing result and what machine code is this error occurring in?
null
The M7114-Timeout waiting for dispensing result error typically occurs when the system is unable to complete a dispensing operation within a specified time limit. The solution may involve troubleshooting the hardware or software, adjusting the time
What is the issue with the KM-FPS error id of 7? Is the X27 machine code related to the solution for this error? What do you need to do to fix the error on the board with X27 machine code?
null
The solution to the error "The board is not flat, please check X27" requires manual inspection of the electrical board to locate any bulges or bumps, causing the board to be uneven. If the component X27 appears anom
What is the issue that is causing the Front stage PLC1-M7021 to have the "Z-axis is not in the safe position during reset" error? What is the KM-ASSYH2-05 error id and what does it mean? How can I resolve the issue
null
The solution to the error "Front stage PLC1-M7021-the Z-axis is not in the safe position during reset" is to perform a return to origin first, which will ensure that the axis is in its safe
What does the M7097 error code mean in the context of a KM-ASSYM5-06 glue barrel position? Why is the cylinder position of the glue barrel abnormal? How can this error be resolved to ensure proper functioning of the glue barrel?
null
M7097 errors occur when the glue barrel's cylinder position is abnormal. To resolve this issue, you can try calibrating the glue barrel, checking for blockage in the cylinder, or performing a manual
What is the error code M7069-Y axis front limit is abnormal and how does it relate to the slide table touching the limit machine code of KM-ASSYM5-06 with error id 70?
null
The solution for M7069-Y axis front limit is abnormal, close to the origin end (X11) is to check whether the slide table touches the limit. The problem could be caused by the slide table moving too far
What action should be taken if the front section PLC1-M7016-EMO&&DOOR is opened and an error message "If the front section PLC1-M7016-EMO&&DOOR is opened, please check the safety door or emergency stop X17
null
The solution for this error is to check the safety door or emergency stop X17 when the front section PLC1-M7016-EMO&&DOOR is opened.
What is the nature of the M133-Failed to take photos of materials on the left tray three times in a row error in the KM-ASSYM2-05 machine code?
null
The solution to the error M133-Failed to take photos of materials on the left tray three times in a row could involve troubleshooting steps such as checking camera settings, ensuring proper lighting, cleaning the camera lens, or restarting
What is the error message displayed in the Front stage PLC1-M7018 with identifier KM-ASSYH2-05? What is the recommended action to resolve this error before starting the automatic process machine code?
null
The solution for the Front stage PLC1-M7018 error described as "Please press the reset button before starting the automatic process" is as follows: Press the reset button before starting the automatic process. This process should restart and run
What is the name of the machine that is being referred to as KM-ASSYH3-07 and what is error id 29?
null
The solution for the error "M7028-EMO&&DOOR is open, please check the safety door or emergency stop?" is to verify that the safety door or emergency stop is closed before operating the machine. If the safety door
What is the error message M111-MAKE point deviation too large and what does it mean for the PCB board?
null
The solution for the error described as The M111-MAKE point deviation is too large is to check whether the PCB board is abnormal by verifying its design, layout, and connection. If the board is found to be
What is the M107-X axis return to origin time timeout machine code of KM-ASSYM5-02 error id of 38, and what does it indicate?
null
The error M107-X axis return to origin timeout indicates that the machine is experiencing a timing issue while returning to the origin position. This error typically occurs when there is a problem with the encoder or motor that is causing the axis to
Here are a few questions that can help with resolving the M7116-Timeout waiting for next action machine code error: 1. What machine or system is generating the error? 2. Can you provide the context in which the error is occurring? 3. Have you checked the logs or
null
The M7116-Timeout waiting for next action error typically occurs when a software process is awaiting user input or a system event but is not receiving it within a specified timeout period. The solution may involve increasing the timeout limit, optimizing
What does error code 16 mean in KM-FPS? What is the stopper cylinder entry rear limit sensor and what does it do? What is X11 machine code and how can it help with error 16? Can you explain how to check the X
null
The solution for the stopper cylinder entry rear limit sensor being abnormal and displaying "please check X11" is to verify the sensor's wiring and ensure that the X11 connector is properly connected. If the
What is the M129-Product Marker 1 point photo failed machine code of KM-ASSYM2-02 error id of 60? How does this error occur in the solution? What does it mean for the product marker 1 point photo to fail? Can the error be
null
The solution for M129-Product Marker 1 point photo failed error is to check if the product marker has been moved or deleted from its original location. If the marker is missing, you can manually add it back by following the steps
What are the possible reasons for the error code M7039, "The left blocking cylinder in the work area is abnormally descending (X41), please check whether the cylinder is stuck when descending" in a KM-ASSYM4-05 machine?
null
The error message M7039-The left blocking cylinder in the work area is abnormally descending (X41), please check whether the cylinder is stuck when descending indicates that there is an issue on a cylinder
What is the context in which you received this error message? Can you provide more information about the solution's functionality and the system environment?
null
The solution for the M145-CCD error is to check the communication with the CCD device and ensure that the necessary signal, D720=1, is being transmitted. The issue could also be resolved by resetting
Can you explain what the M7040 error means and what the X31 flag is associated with? What actions should be taken to troubleshoot this error? Additionally, what is the purpose of checking for a stuck cybernetic machine cylinder when rising a machine with a code id of 41?
null
There are several possible reasons for M7040-The jacking cylinder in the work area rises abnormally. One cause could be a stuck cylinder, which could be due to pressure buildup or debris blocking the cylinder
What are the possible causes of the M7096 error code in weighing machines with KM-ASSYM2-06 error id 97?
null
The M7096 error on a weighing machine indicates communication abnormality. The solution may involve resetting the machine, checking for any software updates, or contacting the manufacturer for further assistance. This issue typically occurs when the machine cannot
What is the cause of the abnormal material alarm in machine M7025, code KM-ASSYH2-07 with error id 26?
null
The solution for the M7025-buffer area abnormal material alarm typically involves performing an inspection of the buffer area or replacing any damaged materials to ensure that the area is functioning properly. If the issue persists, further troubleshooting
What is the meaning of the M80-EMO&&DOOR is on error in the KM-ASSYM5-08 machine code?
null
The solution for the error M80-EMO&&DOOR is on. Please check the safety door and emergency stop switch (X6) is to verify that the safety door is closed and the emergency stop switch is disabled before starting the machine
What is the code for sensor X24 in the machine's KM-ASSYH2-04 error id of 196? What does "The discharging operation of the conveyor belt in the work area has timed out" mean?
null
The solution for the error "Rear section-M7035-The discharging operation of the conveyor belt in the work area has timed out, please check sensor X24" is to ensure that the motor for the
What does the error message M7069-Y axis front limit is abnormal, close to the origin end (X11), mean? How do I check whether the slide table is touching the limit on the Y axis? What is the purpose of checking for this error on the K
null
The solution for M7069-Y axis front limit is abnormal, close to the origin end (X11) is to check whether the slide table touches the limit. The problem could be caused by the slide table moving too far
What is the conveyor belt width adjustment cylinder?
null
The solution for the M7042 error described as "The conveyor belt width adjustment cylinder extends abnormally (X27)" is to check whether the cylinder is stuck when it rises. If the cylinder is
What is the error code M7042-The jacking cylinder in the work area rises abnormally (X44)? What is the meaning of "check whether the cylinder is stuck when rising" as it relates to the machine code of KM-ASSYM
null
The M7042 error occurs when the jacking cylinder in the work area rises abnormally. To resolve the error, check if the cylinder is stuck when it rises. If it is, try to release the cyl
What is the specific error message being displayed and what does it indicate about the issue with the machine code for the KM-ASSYM5-08?
null
The solution for the error described as M123-CCD failed to send signal to arm may vary depending on the specific cause of the issue. It is recommended to consult the manual or contact the manufacturer for further assistance. Possible solutions include
What is the M107-Robot error and how can it be eliminated using machine code?
null
The solution to the M107-Robot error is to use the Robot tool to eliminate the abnormality that triggered the alarm. This can be done by identifying and correcting the cause of the abnormality, such as a
One possible question could be: "What causes the M136-Failed to take pictures with the camera error when programming with the KM-ASSYM5-02 machine code and what possible solutions are available to resolve this issue?"
null
The solution for M136 error could be restarting your device, updating camera drivers, clearing cache and data of camera app, checking if the camera lens is clean, and resetting the camera settings to their defaults. If the problem persists
If the rear section PLC2-M7051 is experiencing a problem with the discharge clamp falling abnormally, it is important to check the sensor-X63 on the KM-ASSYH2-06 machine to identify the root cause of the issue. The following
null
The solution for the error described as Rear section PLC2-M7051 is to check the discharge clamp sensor-X63 for an abnormality. If the sensor is found to be faulty, the cl
What does the M120-Nozzle 2 manual positioning running time timeout error code mean for your machine, KM-ASSYM5-05?
null
The M120 error may occur when the manual positioning of Nozzle 2 exceeds the prescribed time limit. This could be due to several reasons like slow printing speeds, insufficient ink or paper supply, or a software gl
What is the significance of the error M7094-PLC in the context of electronic scale clearing machines?
null
M7094-PLC timed out waiting for the signal from the host computer to complete the electronic scale clearing can be resolved by checking if the host computer is properly connected and also ensuring that there are no delays or issues with the
What is the specific machine and system that is experiencing the blocked_sensor double lights error? What is the purpose of the KM-ASSYM4-03 error identifier, and what are the possible error codes? What is the cause of the blocked_sensor double lights alarm, and what actions can be taken
null
There are several possible causes for this error, including a malfunctioning light sensor or an issue with the camera. However, the most common solution is to clean the affected area thoroughly and try again. If the problem persists, contact the manufacturer or
What is the M7016-EMO error code and what are its possible causes?
null
The solution for this error is to check the safety door or emergency stop, close the door and retest the system. If the problem persists, maintenance or repair may be required. It is recommended to follow the manufacturer's instructions or contact a
What does the "Reset failed alarm machine code of KM-BFT error id of 17" refer to?
null
The "Reset failed alarm" error could be resolved by following these steps: 1. Press and hold the 1 key until the alarm sound stops. 2. Release the 1 key and press and hold the 2 key
What is the error described as M75-Start and what is the work area status machine code of KM-ASSYM3-08 error id of 6?
null
The solution for the M75-Start error is to select the work area status as "Clear" before starting the machine. If the work area is not clear, the machine will not start and will display this error message.
What is the intended solution for the M110-single assembly less than 12 pieces machine code of KM-ASSYM2-08 error id of 41?
null
The M110 error occurs when the number of assemblies being built falls below 12 pieces. Increase the number of assemblies through the project settings, or add additional assemblies to the project. If none of these
What should I do if a printing machine encounters an M7070-Y axis rear limit is abnormal error and the slide table is touching the limit?
null
There are a few possible solutions to address the error M7070-Y axis rear limit is abnormal, far away from the origin end (X12) including: 1. Adjusting the slide table position to ensure
What could be the reasons for the abnormal descent of the conveyor belt width adjustment cylinder in the conveyor system of your KM-ASSYM2-01 machine? Is it possible that the cylinder is stuck or damaged? How can you confirm this during the debugging process? Is there
null
The solution for M7043 errors related to the conveyor belt width adjustment cylinder retracting abnormally (X30) involves checking whether the cylinder is stuck during descent. This issue can cause damage to the convey
What does the error message "The M111-MAKE point deviation is too large, please check whether the PCB board is abnormal machine code of KM-ASSYM3-03 error id of 42" mean?
null
The solution for the error described as The M111-MAKE point deviation is too large is to check whether the PCB board is abnormal by verifying its design, layout, and connection. If the board is found to be
What causes the abnormal extension of the rear section in the M7054 tilt cylinder of the CNC machine? What information can be obtained from the sensor X62 in KM-ASSYH2-04 error id 215?
null
The solution for the error described as Rear section-M7054-tilt cylinder-rising (middle), abnormal extension, please check sensor X62 is to reset the sensor X62 and check its connection.
What does it mean for nozzle 1&2-Z axis origin sensor abnormality to occur on a machine with a PLC2-X0, X2 error code of 57? How might this error affect the functionality of the machine and what steps could be taken to address it?
null
The solution for M126-Nozzle 1&2-Z axis origin sensor abnormality (PLC2-X0, X2) involves calibrating the Z-axis sensors and adjusting the nozzle
What does error code M115-Nozzle 1 automatic positioning running time timeout mean in the context of KM-ASSYM3-05? How long did the automatic positioning process take to complete without a successful response from the machine? What steps can be taken to resolve this issue
null
The solution for M115-Nozzle 1 automatic positioning running time timeout error is to check the printer's settings and configuration to ensure that the printer is set up to wait long enough for the automatic positioning process to complete
What is the location and function of sensor X51 on the conveyor belt of the PLC1-M7034 system? What is KM-ASSYH2-06 system, and what is the error id of 35 associated with it? Describe the work area of the convey
null
The solution for the described error is to reset the conveyor belt and check the sensor X51. If the sensor is not functioning properly, it should be replaced or repaired to allow the conveyor belt to resume its feeding operation.
What is the specific error message being displayed? What does it mean for there to be a communication abnormality between the front-end and M7021-PLC machine code? What is the purpose of these components and how are they typically used in a manufacturing process? Are there any known workarounds
null
Communication abnormality between front-end-M7021-PLC error typically occurs when the front-end device cannot connect to the back-end device, such as a PLC or control system. This issue can be resolved
What error code is generated when the rear section PLC2-M7016-EMO&&DOOR of the X17 machine is opened and a safety door or emergency stop is activated?
null
The solution for the error you described is to ensure that the safety door or emergency stop X17 is functioning properly and has not been triggered when the PLC2-M7016-EMO&&DOOR section is opened. This
What is the error message M124-CCD and what is the arm machine code of KM-ASSYM3-08? What is the error id of 55? Also, what is the function related to the READY signal in the context of an arm machine?
null
This error usually indicates a hardware issue with the CCD camera controller in your robot arm. It may require updating or reprogramming the controller's firmware or software, or troubleshooting the controller's connections to ensure the arm receives
What is the error being described in relation to a Front section-M7048-upper cover side positioning cylinder (middle) on a KM-ASSYH2-04 machine?
null
The solution for the Front section-M7048-upper cover side positioning cylinder (middle), abnormal extension, please check sensor X54 error is to repair or replace the faulty sensor (X54) and reset
Can you provide some additional context on the error message? What is the error code "Rear section-M7058-upper cover front positioning cylinder-extension (rear), extension is abnormal, please check sensor X67 machine code of KM-ASSYH2-04
null
The solution to the error "Rear section-M7058-upper cover front positioning cylinder-extension (rear), extension is abnormal, please check sensor X67" is to inspect and test Sensor X6
What is the equipment that is causing the M7004 alarm and the KM-ASSYM5-08 error id of 119? What is the nature of the alarm and what is the purpose of the error code? What should be done to resolve the issue and
null
The solution for M7004-Equipment alarming error would depend on the specific piece of equipment and issue causing it. It could be resolved by performing maintenance or repairs, checking connections or sensors, resetting parameters, or updating software
1. What is the function of the discharge point in the circuit being analyzed? 2. Can you provide more information about the circuit being analyzed, such as its design and the type of equipment being used? 3. What is the possible cause of the error code M7115? 4
null
The error "M7115-The discharge point exceeds the index range" indicates a problem in the discharge of stored procedures. To resolve this issue, you can check the discharge point value and modify it within the index range
What is the cause of the M141-CCD timed out error when machine code D228=1 is not received?
null
The solution for this error is to check that there are no obstacles blocking the nozzle pickup sensor and make sure the sensor is functioning properly. If the issue persists, consider resetting the printer.
What is the nature of the abnormal opening of the safety door during the return to origin machine code function of the KM-ASSYH1-07 controller?
null
The solution for the error described as M7028-Safety door opens abnormally during return to origin requires an inspection of the safety door drive system for any damage or malfunction. The door may need to be adjusted or replaced
What is the M7030-PLC1 and PLC2? How are they related in the KM-ASSYH2-07 error id 191? Can you provide more context about the error message? What does the "communication abnormality" refer to? Is
null
The solution for the communication abnormality between M7030-PLC1 and PLC2 would depend on the specific error and its underlying cause. Some possible solutions include checking the communication settings, diagnosing hardware issues, and ensuring that
What is the conveyor belt width adjustment cylinder, and how is it controlled in the KM-ASSYM5-01 machine? What could cause the cylinder to extend abnormally, and what is the possible cause of the M7042 error? What should be done to diagn
null
The solution for the M7042 error described as "The conveyor belt width adjustment cylinder extends abnormally (X27)" is to check whether the cylinder is stuck when it rises. If the cylinder is
What is the error message you received when attempting to communicate with the Kazam solution?
null
The solution for the "Kazam communication failed" error may vary depending on the specific cause of the issue. It could be due to an incorrect or outdated configuration, lack of permissions, or connectivity problems. Checking the Kazam server
What is the M7036 error message and what does it mean in terms of the machine code KM-ASSYM5-01 with error id of 37?
null
The solution for the M7036 error is to check the rear buffer conveyor belt for jams or obstructions. If the belt is jammed, clear the obstruction and try running the belt again. If the belt continues to jam
What is the error message "M7005-Pass function is enabled machine code of KM-ASSYM2-03 error id of 120"?
null
M7005 error means that the Pass function is enabled in your Excel spreadsheet. To fix this error, you need to disable the Pass function by going to the "Worksheet" tab and clicking on "Properties". In the "
What is the specific issue you are encountering with the M150-PLC timed out error when trying to communicate with the CCD (camera) through the KM-ASSYM5-05 machine code? Have you confirmed that the CCD is properly connected and functioning? Additionally, what
null
The solution to M150-PLC timed out while waiting for CCD to send the retrieval command could be to increase the timeout value in the PLC programming or to add a delay between the CCD command and the PLC
What is the abnormality detected in the KM-ASSYM2-03 machine code, and how can the Robot program be used to eliminate it?
null
The solution to the M107-Robot error is to use the Robot tool to eliminate the abnormality that triggered the alarm. This can be done by identifying and correcting the cause of the abnormality, such as a
What possible reasons could cause the manual positioning running time timeout in machine code M114-Nozzle 1 manual positioning running time timeout on KM-ASSYM3-05 error id 45? Possible reasons for the manual positioning running time timeout error code
null
The M114-Nozzle 1 manual positioning running time timeout error indicates that the system took too long to respond to a manual positioning request for Nozzle 1. To resolve this issue, check the nozzle
What is the possible cause of the error message M7034 in the KM-ASSYM1-05 machine code of error id 35?
null
The M7034 error message indicates that the conveyor belt feeding operation has timed out. To resolve this issue, first, check if the machine is jammed. Clear any blockages or jams from the conveyor belt. If
What is the machine code for the KM-ASSYM2-01 error id of 17?
null
The solution for the error described as M7016-EMO&&DOOR is on, is to check the safety door and emergency stop switch (X22). If either of these components is faulty, it can cause the error
What problem is being reported? Can you provide more details about the equipment and software being used? Have you tried any troubleshooting steps?
null
The M7104 error indicates that the host computer failed to read the READ signal sent by TE (Telecom Equipment) and resulted in a LINK fail. This issue may occur when the fiber optic cable is damaged, or there is
Here are some possible questions related to the error in the solution you described: 1. What is the error message in the solution for this issue? 2. What is the issue being described in the solution? 3. How does the middle push PCB cylinder-retract problem relate to the ab
null
The error Rear section-M7053-push PCB cylinder-retract (middle), retraction is abnormal, please check sensor X61 indicates a problem with the sensor X61. Check the sensor for potential
What error message has been reported with the M7023-product on left slide nozzle error? Also, what product was found on the left slide nozzle, and how was it taken off? Additionally, what is the KM-ASSYH1-03 error code, and what
null
The solution for M7023 error is to remove the product from the left slide nozzle and turn off the vacuum suction.
What is the meaning of "Previous PLC1-M7019-The equipment has not returned to the origin, please perform the equipment return to the origin first" error text? Why did the machine generate this error? What are the possible causes of this error? What are
null
The solution to the error "Previous PLC1-M7019-The equipment has not returned to the origin, please perform the equipment return to the origin first" is to first perform the equipment return to the origin before proceeding with
What is the specific machine or system that generated the M96- Abnormal rise of jacking cylinder in work area (X22) error code? What is the machine model or type that produced the error code KM-ASSYM5-10? What are the possible
null
The solution for the M96 error code "Abnormal rise of jacking cylinder in work area (X22)" would typically involve performing a thorough inspection of the equipment to identify any faulty components or loose connections. Once the cause of